The bugs published on this page are mainly computational bugs that affect the calculation results. There should be a bug fix patch for each bug, or at least a plan for when the bug will be fixed.

As a service to our customers we also make patches for other bugs reported to us. We do not publish these patches on this page but send them directly to customers reporting the problem.

 

How to get a patch
To get a download link to a patch and installation instructions, please email us at ice.support@equa.se
Make sure to include the patch number.

 

October 17, 2017

Pumping power: If method ”Performance polynomial: Riding the pump curve” is selected the pumping power is incorrect.

Introduced in IDA ICE 4.7.1 (patch for IDA ICE 4.7.1 available)
Patch no: 171017
Will be fixed in IDA ICE 4.8


September 29, 2017

Borehole extension: The pressure drop calculation is not correct. The pressure drop, dp, should be multiplied with 2.

Introduced in Borehole-1.1
Will be fixed in Borehole-1.2


May 2, 2017

Lokalisierung Schweiz: Das SIA 2028 normale „Design Reference Year“ von Pully (städtische Südhanglage westliches Mittelland) ist falsch. Die Daten entsprechen stattdessen denjenigen von der Klimastation Piotta (Tallage Alpensüdseite).

Introduced in Localization Switzerland 4.7 (patch for Localization Switzerland 4.7.1 available)
Patch no: 170502


May 1, 2017

Lokalisierung Schweiz: Wenn im Modell eine wassergeführte Kühlung definiert ist, wird diese für das automatisch erstellte Modell für den Nachweis SIA 180 C.1 „sommerlicher Wärmeschutz“ nicht entfernt. Das Nachweismodell weist somit weiterhin eine Kühlung aus, welche manuell zu entfernen ist.

Introduced in Localization Switzerland 4.7 (patch for Localization Switzerland 4.7.1 available)
Patch no: 170501


April 20, 2017

Window shading on sloped roof windows from imported shading objects is incorrectly calculated. This can potentially lead to errors in the zone heat balance.

Introduced in IDA ICE 4.0
Will be fixed in IDA ICE 4.8


December 21, 2016

Time-split parallelization: When using time-split parallelization and the simulation period overlaps more than one calendar year, a time-split period may become incorrect if it is wholly within the second year.

Introduced in IDA ICE 4.7
Will be fixed in IDA ICE 4.8


December 6, 2016

Exhaust air heat recovery (new AHU and corresponding ESBO plant component in 4.7.1):

  • The mass flow in the liquid circuit may become wrong.

  • The design temperature difference parameter in the ESBO plant is not available at the standard level.

  • Design conditions that do not lead to condensation are rejected.

The model still delivers physically correct results, but the design operating point becomes different from that intended.

Introduced in IDA ICE 4.7.1 (patch for IDA ICE 4.7.1 available)
Patch no: 161206
Will be fixed in IDA ICE 4.8


November 23, 2016

Integrated shadings in the outer window of a double façade:

  • For a venetian blind, the slat angle is always 45°, regardless of set angle.

  • If the control “Sun” is chosen, the shading is always drawn.

  • If the control “Sun AND Schedule” is set, the shading is controlled by the irradiation level on the inside of the window, regardless of what is chosen.

  • If “New custom control” (ShadeCtrlMacro) is chosen and “Combined with built-in light control” is marked, the light control is ignored.

Introduced in IDA ICE 4.7 (patch for IDA ICE 4.7 & 4.7.1 available)
Patch no: 161123
Will be fixed in IDA ICE 4.8


November 21, 2016

Deutsche Lokalisation, DIN 4108-2 Add-In: Wenn für eine Zone des Ausgangsmodells unter "In Betrieb" die Voreinstellung "Wenn belegt" durch einen Zeitplan ersetzt wird so wird diese Einstellung im DIN 4108-2 Nachweismodel beibehalten. Korrekte Übertemperaturgradstunden erhält man nur wenn im Nachweismodell der Wert wieder auf "wenn belegt" eingestellt wird.


Introduced in Localization Germany 4.6.1 (patch for Localization Germany 4.7.1 available)
Patch no: 161122


November 21, 2016

Zone multipliers: In the table "Energy balance (sensible only)" in the “Summary” tab, zone multipliers are ignored in the results. In all other summarizing results they are used.

Introduced in IDA ICE 4.7 (patch for IDA ICE 4.7 & 4.7.1 available)
Patch no: 161121
Will be fixed in IDA ICE 4.8


November 17, 2016

Wall model: When inserting a “Heating/cooling floor” in an edited (complex) roof, an RCWALL model with default parameters (except the area) is wrongly used.

Introduced in IDA ICE 4.0 (patch for IDA ICE 4.7 & 4.7.1 available)
Patch no: 161117
Will be fixed in IDA ICE 4.8


November 16, 2016

Window area: The area of non-rectangular windows and openings inserted in faces of the building body is not correctly calculated.

Introduced in IDA ICE 4.0 (patch for IDA ICE 4.7 & 4.7.1 available)
Patch no: 161116
Will be fixed in IDA ICE 4.8


November 15, 2016

Simulation time: When setting the simulation time, the date is switched incorrectly if the starting time is late in the day or the ending time is early in the day.

Introduced in IDA ICE 4.7.1 (patch for IDA ICE 4.7.1 available)
Patch no: 161115
Will be fixed in IDA ICE 4.8


November 14, 2016

Daylighting: When selecting “Daylighting” in the “Requested output” under the “Simulation” tab, a simplified calculation of the illuminance in zones with an occupant present is performed. When using the detailed window model with an integrated shading that diffuses the light, the solar (total shortwave) properties are used instead of the visual properties for the diffused light. Note that this bug does not affect the daylight calculation performed under the “Daylight” tab.

External shading: When setting the control of an external solar shading to a value in between 1 and 0 (which are the values normally used for on/off), the result deviate from the expected weighted average of the results for 1 and 0.

Miljöbyggnad: The value of “g-syst”, given in “Miljöbyggnad”, includes, when using the standard window, solar heat transferred though the frame, which is not according to the rules of “Miljöbyggnad”.

Introduced in IDA ICE 4.7.1 / 4.0 / 4.7 (patch for IDA ICE 4.7.1 available)
Patch no: 161114
Will be fixed in IDA ICE 4.8


November 8, 2016

Autosave: The Autosave function does not start to work until after a first simulation has been performed.

Introduced in IDA ICE 4.7 (patch for IDA ICE 4.7 & 4.7.1 available)
Patch no: 161108
Will be fixed in IDA ICE 4.8


October 18, 2016

Deutsche Lokalisation, DIN 4108-2 Add-In: Bei Nichtwohngebäuden wird der Zeitplan "din41082-7-18 weekdays" konstant als "0" angesetzt, auch wenn wochentags zwischen 07:00 Uhr und 18:00 Uhr der Wert "1" angezeigt wird. Dies hat fundamentale Auswirkungen auf die Berechnung.

Introduced in Localization Germany 4.7.1 (patch for Localization Germany 4.7.1 available)
Patch no: 161103


June 27, 2016

Daylight: Calculation of daylight for windows with active (drawn) integrated solar shading can in some cases, especially for darker (low-reflective) shadings, give too high values.

Introduced in IDA ICE 4.7
Fixed in IDA ICE 4.7.1


May 4, 2016

Markisolette: When using the external shading of the type “Markisolette”, the upper part of the shading will be in line with the outer glazing and therefore ignored unless a recess depth is set for the window. This can be avoided by setting a small recess depth (1 mm or more).

Introduced in IDA ICE 4.7
Fixed in IDA ICE 4.7.1


May 4, 2016

Daylight: When using external shadings, e.g. “Markisolette” or “Drop arm awning”, the daylight calculation will always be made with the shadings drawn, even when “Controllable shading” is set otherwise. This can be avoided by removing the external shadings before the daylight calculation.

Introduced in IDA ICE 4.7
Fixed in IDA ICE 4.7.1


April 22, 2016

Daylighting: When selecting “Daylighting” in the “Requested output” under the “Simulation” tab, a simplified calculation of the illuminance in zones with an occupant present is performed. The results from this calculation are too high when using the detailed window model. Note that this bug does not affect the detailed daylight calculation performed under the “Daylight” tab.

Introduced in IDA ICE 4.0 (patch for IDA ICE 4.7 available)
Patch no: 160421
Fixed in IDA ICE 4.7.1


March 15, 2016

Daylight:

  • Imported images are included in the Radiance daylight calculation as shading surfaces with total reflection. This can potentially lead to very incorrect daylight levels.

  • The size of the Radiance scene is incorrect if non-shading objects are placed far away from the measuring plane or if a section of the 3d view has been created with the x+, x-, y+, y-, z+, z- buttons prior to the daylight calculation. This can potentially lead to incorrect daylight levels.

  • Parallel Radiance daylight calculation processes are not aborted when the daylight calculation is aborted.

Introduced in IDA ICE 4.7 (patch for IDA ICE 4.7 available)
Patch no: 160315
Fixed in IDA ICE 4.7.1


March 7, 2016

Thermal bridges: Angles different from 90° in corners are compensated the wrong way by making the length of the thermal bridge longer instead of shorter for larger angles. This means for example that a round building, with a lot of obtuse angles, will have disproportionately long thermal bridges. The important special case of an 180 degree angle (an accidental break point) is treated correctly (no thermal bridge). Note that the combined length of thermal bridges is presented in the zone form under Loss factor for thermal bridges and can be edited there.

Introduced in IDA ICE 4.5 (patch for IDA ICE 4.7 available)
Patch no: 160307
Fixed in IDA ICE 4.7.1


March 2, 2016

Energy zone model: The convective heat transfer from occupants is calculated using the operative temperature instead of the air temperature of the zone.

Introduced in IDA ICE 4.0 (patch for IDA ICE 4.7 available)
Patch no: 160225
Fixed in IDA ICE 4.7.1


March 2, 2016

Infiltration: A bug in the conversion of units defined per "Air-wetted external surface area" to other units has the following consequences: If "Distribute proportional to" is set to "Air-wetted external surface area", the distribution will instead be (close to) proportional to the total external surface area, and if the set infiltration rate is given per air-wetted external surface, this is instead treated as given per total external surface area (or close to this).

Introduced in IDA ICE 4.6
Fixed in IDA ICE 4.7


March 2, 2016

Both window models: The heat resistance of the window frame material is limited to 1/5.8 m2K/W (instead of 1/5.8 - 0.17 m2K/W). This limits the U-value of window frames to 2.9 W/m2K (instead of 5.8 W/m2K).

Introduced in IDA ICE 4.0 (build 3)
Fixed in IDA ICE 4.7


November 19, 2015

With the new Acrobat Reader DC (version 2015.007.20033), IDA ICE crashes uncontrolled after opening PDF documentation in the online help.

In all IDA ICE versions up until 4.6.2 (patch for IDA ICE 4.6.2 available)
Fixed in IDA ICE 4.7

 


 


>